Product Name: Specialized Corrosion Inhibitor for Secondary-Side Cooling Loops (Glycol-Based)
Model: SGR0844
Description: This product is a specialized, multi-component composite corrosion inhibitor developed for the secondary-side ethylene glycol cooling loops in liquid-cooling CDU (Coolant Distribution Unit) systems for computing centers. It appears as a uniform, transparent liquid. Designed specifically to address metal corrosion in secondary-side ethylene glycol circulation systems—including chillers, plate heat exchangers, piping networks, and pumps—it provides comprehensive protection for common materials such as carbon steel, copper, copper alloys, and stainless steel. It effectively suppresses chemical corrosion caused by the hydrolysis and acidification of ethylene glycol, as well as galvanic corrosion resulting from the use of multiple, dissimilar metals. This significantly enhances the operational stability of CDU systems, extends the service life of cooling equipment and piping, and reduces both equipment downtime and maintenance costs in data centers.

Physical and Chemical Properties:
Product Appearance | Colorless to pale yellow transparent liquid |
pH (1% aqueous solution) | ≥9.0 |
Density (20°C, g/cm³) | ≥1.10 |
Performance:
① High-Efficiency Corrosion Inhibition: Precisely formulated for the corrosive characteristics of ethylene glycol aqueous solutions, achieving an overall corrosion inhibition rate of over 99.8%. It effectively prevents rust, pitting, perforation, and leakage in piping.
② Excellent Compatibility: Fully compatible with standard industrial ethylene glycol-based coolants/antifreezes. It does not compromise the antifreeze properties of the glycol, nor does it cause scaling, flocculation, or blockages in heat exchanger channels.
③ Long-Term Stability: Well-suited for the continuous, long-term operation typical of data center environments, with excellent chemical persistence.
④ No Impact on Heat Transfer: The additive does not increase the viscosity of the fluid or form deposits on heat exchanger surfaces, ensuring high-efficiency heat transfer in chillers and CDU plate heat exchangers without compromising the cooling performance of the facility. Application: Designed for the secondary-side closed-loop ethylene glycol cooling systems of data center CDU (Coolant Distribution Unit) setups, including the complete circulation loop for cold plates. It is suitable for data center environments that require constant-temperature operation year-round or seasonal switching between winter and summer cooling modes. It provides effective protection for all conventional metals present within the system.
Usage: The dosage must be calculated strictly based on the total volume of the ethylene glycol aqueous solution in the system. Specific guidelines are provided for new systems, older systems with existing corrosion, and routine maintenance, aligning with standardized data center operations and maintenance (O&M) procedures.
① Initial Dosing for Newly Installed CDU Cooling Systems
For new, clean, and corrosion-free ethylene glycol circulation systems, add 2–3 kg of this product per cubic meter of the ethylene glycol aqueous solution. Calculate the total required amount based on the system's total volume, inject it slowly into the circulation loop, and run the system's circulation pump for at least 30 minutes to ensure the product is thoroughly and uniformly mixed with the coolant.
② Initial Dosing for Older, Corroded Systems
For CDU cooling systems that have been in operation for a long time and exhibit minor rust or corrosion, add 5–6 kg of this product per cubic meter of the ethylene glycol aqueous solution. The dosage may be adjusted based on the severity of pipeline corrosion or the turbidity of the fluid. Add the full amount at once and circulate thoroughly to effectively suppress any residual corrosion risks.
③ Routine Maintenance Dosing (Replenishment)
During normal, continuous system operation, add a replenishment dose once every four months. Use a dosage of 1–2 kg of this product per cubic meter of the ethylene glycol aqueous solution to compensate for any loss of the chemical agent and to maintain the system's anti-corrosion performance.